What’s included
Private fire service mains from the connection at the street to the riser.
Hydrants installed, flow tested and maintained across your site.
FDCs that let the fire department boost your system with their own pumps.
New underground is flushed and hydrostatically tested before it ties into the system.
Standards & intervals
Common tests for underground mains, hydrants and connections.
| Activity | Interval | Standard |
|---|---|---|
| New underground | Flush, then hydrostatic test at 200 psi for 2 hours | NFPA 24 |
| Private hydrants | Annual flow test & inspection | NFPA 25 |
| Underground & exposed piping | Flow test every 5 years | NFPA 25 |
| Fire department connection | Quarterly inspection | NFPA 25 |
Questions
Yes. NFPA 25 calls for annual flow testing and inspection of private hydrants.
Yes. The private fire service main is installed and the connection coordinated with your utility and general contractor.