If your building has a sprinkler system, it’s covered by NFPA 25 — the standard for inspection, testing and maintenance (ITM) of water-based fire protection systems. Fire marshals enforce it, and your insurer will usually ask for proof you’re following it. Once you know what’s due when, most of it is routine.

The schedule at a glance

How oftenWhat gets checked
MonthlyGauges and control valves
QuarterlyAlarm devices and fire department connections
SemiannuallyWaterflow alarm and valve supervisory switch tests
AnnuallySprinklers, pipe, fittings and hangers from the floor; main drain test; antifreeze solution; dry pipe valve partial trip test; fire pump flow test
Every 3 yearsDry pipe valve full trip test
Every 5 yearsInternal pipe assessment for obstructions; gauges replaced or recalibrated
By sprinkler ageFast-response heads sampled at 20 years, standard heads at 50, dry sprinklers at 10 — then every 10 years

Fire pumps add their own routine: a no-flow “churn” test weekly or monthly depending on the driver, and a full flow test once a year.

Editions matter

Your jurisdiction adopts a specific edition of NFPA 25, and some intervals have changed between editions. We schedule to the edition your fire marshal enforces, not a generic checklist.

Who can do the work

In Texas, sprinkler inspection and testing is performed by contractors licensed through the State Fire Marshal’s Office. Each completed inspection gets a service tag on the riser, and you get a written report listing every deficiency.

What happens if you miss one

Missed inspections are one of the most common citations a fire marshal writes, and gaps in your records can complicate an insurance claim after a loss. Small problems also get bigger: a corroded valve or a failing gauge is cheap to fix during a routine visit and expensive to fix in an emergency.

How we keep you on schedule

Every system we service goes on a recurring calendar. We send reminders before anything is due, and every report is posted to your customer portal so you can hand it to an inspector in seconds.

Protect your people and property.

Talk to a Safe Life specialist about your facility today.

How Often Does Your Fire Sprinkler System Need Inspection?